In the purchase of diesel generator sets, many users are confused about power. Some bad merchants on the market will also use their lack of understanding of power to set purchase traps, which leads to people making wrong judgments when purchasing. Haixing Power, a professional diesel generator set manufacturer, will analyze the relevant knowledge of diesel generator set power for you in detail.
The basis for engine power calibration is mechanical strength, thermal load strength, and fatigue life. The same generator set can be calibrated to different powers according to the load rate and the length of use time.
GB2820-2009 is equivalent to standard ISO8528 and is divided into four powers according to the usage requirements:
1. ESP, emergency backup power
2, LTP, limited-time operation power
3, PRP, basic power
4, COP, continuous power
emergency backup power (ESP)
. Emergency backup power is defined as: maintenance is carried out under agreed operating conditions and according to the maintenance intervals and methods specified by the manufacturer. When the public power grid fails or under test conditions, the generator set operates for 200 hours per year.
The allowed average output power (Ppp) during the 24-hour operation period shall not exceed 70% of the ESP unless otherwise specified by the reciprocating internal combustion (RIC) machine manufacturer.
Limited time operation power
Limited time operation power is defined as: the maximum power of the generator set to power up to 500 hours per year under agreed operating conditions and in accordance with the maintenance intervals and methods specified by the manufacturer.
Note: The operating time according to the limited-time operating power (LTP) shall not exceed 500 hours per year.
Basic Power
Basic Power is defined as the maximum power that the generator set can continuously power the variable load without limiting the annual operating time under agreed operating conditions and in accordance with the manufacturer's specified maintenance intervals and methods.
The permissible average output power (Ppp) within a 24-hour cycle should not exceed 70% of the PRP unless otherwise specified by the reciprocating internal combustion (RIC) machine manufacturer.
Note: Continuous power (COP) may be used when the required permissible Ppp is greater than the specified value.
Continuous Power (COP)
Continuous Power is defined as the maximum power that the generator set continuously supplies constant power to a constant load under agreed operating conditions and in accordance with the manufacturer's specified maintenance intervals and methods.
If you want to further understand the knowledge of diesel generator sets, please follow the official WeChat account of Haixing Power. The staff will gradually push technical knowledge, maintenance and repair, procurement tips and other content to help you become familiar with the operation of diesel generator sets and give full play to the role of diesel generator sets. We look forward to your attention!