18553382068 13951158508
News Center
front page / News Center / Technical support / Treatment measures for water cut off from generator sets

Treatment measures for water cut off from generator sets

Views: 0     Author: Site Editor     Publish Time: 2014-08-01      Origin: Site

Inquire

wechat sharing button
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

The frequent high temperatures in summer make everyone not only pay attention to the abnormal temperature of the generator set, but also prevent the occurrence of water cuts. If there is a water cut during operation, how to implement treatment measures? Haixing Power introduces to you:

During operation, when the generator set is out of the water cut signal, the operating personnel should immediately look forward to the time and prepare for the accident of water cut off protection and refusal; at the same time, find out the cause and restore water supply as soon as possible. If the cooling water is restored within 20S, a comprehensive inspection of the cooling system and various parameters should be carried out, especially the water supply of the stator coil. If the water flow is not running, the water inlet pressure should be increased immediately to restore the water supply or immediately un-order and shut down; if the water cut-off time reaches 20S and the water cut-off protection refuses to move, the motor circuit breaker and incoming switch should be pulled manually immediately.

More than 20 years of experience in gas power generation engineering application. It has the ability to provide integrated operation services of technology, equipment, engineering design, construction, operation and services.

Contact us

18553382068
13951158508
2260661851@qq.com
2260661851
www.hxdlkj.com
all rights reserved Su ICP No. 19030651-1 Sitemap