Frequent high-temperature weather in summer requires everyone to pay attention to the abnormal temperature of the generator set and also to prevent water outages. If you encounter a water outage during operation, how to deal with it? Haixing Power introduces to you:
Running,Generator setWhen the water cutoff signal is sent out, operators should immediately check the time and be prepared to deal with the accident if the water cutoff protection fails to operate; at the same time, find out the cause and restore water supply as soon as possible. If the cooling water is restored within 20S, a comprehensive inspection of the cooling system and various parameters should be carried out, especially the water supply of the stator coil. If the water flow is found to be blocked, the inlet water pressure should be immediately increased to restore the water supply or the train should be immediately decoupled and shut down; if the water cutoff time reaches If the water cutoff protection refuses to operate after 20 seconds, the generator circuit breaker and magnetic switch should be opened manually immediately.