1. Product Overview
135 biogas generator set isThe voltage of Jiangsu Haixing Power Engineering Company is 400/1200V, the single unit power range is 20-800KW, and the frequency is 50HZ gas generator sets. They are widely used in oil fields, coal mines and other industries. The advantages of 1200V voltage are high voltage and small line loss. The manufacturing standards refer to the relevant provisions of the national standard 'GB2820 General Technical Conditions for Power Frequency Diesel Generator Sets'. This series of units has the characteristics of high voltage regulation accuracy, good dynamic performance, small voltage waveform, high efficiency, compact structure, convenient maintenance, reliable operation, and good economic performance.
2. Principle of biogas power generation
The process of biogas power generation using microbial metabolism to produce various products is called fermentation. Biogas fermentation, also known as anaerobic digestion, anaerobic fermentation and methane fermentation, refers to the process of organic matter (such as human, livestock and poultry manure, straw, weeds, etc.) , and complex organisms that form mixed gases (biogas) such as methane and carbon dioxide through the catabolism of various microorganisms with different functions. The collected biogas passes throughGenerator setThe engine performs combustion work, which is the form of an internal combustion engine. The torque after work drives the rotor windings of the generator to work, completing the power generation process.
3. Biogas requirements of 135 biogas generator set
The impurity content in biogas such as Si, HS, etc. should be controlled within the corresponding range. The temperature of biogas is 10~60 ℃ and the pressure is 0~5kpa. Generally, biogas treated anaerobically of poultry and livestock manure can meet the temperament requirements of power generation. Sewage Treatment of biogas requires desulfurization and other treatments, while landfill biogas requires dehydration and other treatments.
4. Precautions for use
Do not add more engine oil than the highest mark on the dipstick. Overfilling may cause damage to the engine.
Refill new engine oil from the filling port (in the direction of the arrow). After filling, start the engine and let it run at low speed for a few minutes
Used engine oil and oil filters are service waste. To prevent environmental pollution, regulations should be followed.
In some cases, if you need to open the cooling ducts while the engine is hot, read the manufacturer's instructions carefully.
5. Company Profile
Jiangsu Haixing Power Engineering Co., Ltd., located in Guxi Industrial Park, Taixing City, Jiangsu Province, is a professional manufacturer integrating the production, sales and maintenance of generator sets. The company mainly produces Dongfeng Fengshen generator sets, Dongfeng Cummins generator sets, Dongfeng Renault generator sets and Volvo generator sets, among which Dongfeng Cummins generator sets are sold at home and abroad.
Since its establishment, the company has continuously focused on the technical research and development of 135 biogas generator sets, expanded production scale, improved generator set-related services, and gradually developed into a new modern private enterprise in Taizhou City. The company has a complete organization and management system, rich human resources, advanced technology research and development and process equipment capabilities, and complete testing equipment. The 'Haixing' brand 20-2000Kw diesel generator sets produced are widely used in shipping, petrochemical industry, highways, railways, water conservancy hubs, municipal engineering, postal and telecommunications, industrial and mining enterprises, hotels and other fields.
6. Main parameters
Generator set model | Engine model | Generator model | Rated power(KW) | Maximum output power | Speed(r/min) | form | Cylinder volume (L) | Bore/stroke mm | Piston speed (m/s) | Intake method/combustion system |
24GFT49 | 2135T | IFC6-185-4 | 24 | 30 | 1500 | 4 stroke inline 2 cylinder | 4 | 135/140 | 7 | Naturally aspirated, non-supercharged/electronic ignition |
30GFT50 | 2135T | IFC6-223-4 | 30 | 37 | 1500 | 4 stroke inline 2 cylinder | 4.3 | 135/150 | 7.5 | |
40GFT51 | 4135T | IFC6-224-4 | 40 | 59 | 1500 | 4 stroke inline 2 cylinder | 8 | 135/140 | 7 | |
50GFT52 | 4135T | IFC6-225-4 | 50 | 73 | 1500 | 4 stroke inline 2 cylinder | 8.6 | 135/150 | 7.5 | |
64GFT22 | 6135T-1 | IFC6-226-4 | 64 | 83 | 1500 | 4 stroke inline 2 cylinder | 2 | 135/140 | 7 | |
75GFT60 | 6135T-2 | IFC6-282-4 | 75 | 88 | 1500 | 4 stroke inline 2 cylinder | 12 | 135/140 | 7 | |
90GFT32 | 6135T-1 | IFC6-283-4 | 90 | 110 | 1500 | 4 stroke inline 2 cylinder | 12.9 | 135/150 | 7.5 | |
100GFT35 | 6135T-2 | IFC6-283-4 | 100 | 120 | 1500 | 4 stroke inline 2 cylinder | 12.9 | 135/150 | 7.5 | |
120GFT54 | 6138AT-2 | IFC6-284-4 | 120 | 139 | 1500 | 4 stroke inline 2 cylinder | 13.9 | 138/163 | 8.1 | |
150GFT57 | 12V135T | IFC6-286-4 | 150 | 170 | 1500 | 4 stroke inline 2 cylinder | 24 | 135/140 | 7 | |
250GFT61 | 12V138AT | IFC6-353-4 | 250 | 280 | 1500 | 4 stroke inline 2 cylinder | 27.6 | 138/155 | 7.9 |
Generator set model | Compression ratio | direction of rotation | Total oil capacity (L) | Total cooling water capacity (L) | cooling system | Exhaust smoke temperature | Operation type | Natural gas consumption (m3/h) | Engine oil consumption (liter/hour) |
24GFT49 | 11 | Counterclockwise rotation when viewed from the direction of the flywheel | 20 | 100 | Water cooling/50% purified water plus 50% ethylene glycol-based antifreeze/inhibitor | ≤430 | Continuous power generation, as long line or base load power supply | 7 | 0.04 |
30GFT50 | 11 | 20 | 100 | ≤440 | 8.6 | 0.041 | |||
40GFT51 | 10 | 20 | 120 | ≤420 | 11.5 | 0.07 | |||
50GFT52 | 10 | 20 | 120 | ≤430 | 14.2 | 0.08 | |||
64GFT22 | 10.5:1 | 30 | 150 | ≤450 | 18.2 | 0.08 | |||
75GFT60 | 10.5:1 | 30 | 150 | ≤470 | 21 | 0.083 | |||
90GFT32 | 10.5:1 | 30 | 150 | ≤500 | 25.3 | 0.089 | |||
100GFT35 | 10.5:1 | 30 | 150 | ≤530 | 28 | 0.09 | |||
120GFT54 | 10.5:1 | 30 | 150 | ≤550 | 33 | 0.099 | |||
150GFT57 | 10.5:1 | 30 | 210 | ≤470 | 41 | 0.105 | |||
250GFT61 | 10.5:1 | 60 | 300 | ≤585 | 70 | 0.2 |
1. Product Overview
135 biogas generator set isThe voltage of Jiangsu Haixing Power Engineering Company is 400/1200V, the single unit power range is 20-800KW, and the frequency is 50HZ gas generator sets. They are widely used in oil fields, coal mines and other industries. The advantages of 1200V voltage are high voltage and small line loss. The manufacturing standards refer to the relevant provisions of the national standard 'GB2820 General Technical Conditions for Power Frequency Diesel Generator Sets'. This series of units has the characteristics of high voltage regulation accuracy, good dynamic performance, small voltage waveform, high efficiency, compact structure, convenient maintenance, reliable operation, and good economic performance.
2. Principle of biogas power generation
The process of biogas power generation using microbial metabolism to produce various products is called fermentation. Biogas fermentation, also known as anaerobic digestion, anaerobic fermentation and methane fermentation, refers to the process of organic matter (such as human, livestock and poultry manure, straw, weeds, etc.) , and complex organisms that form mixed gases (biogas) such as methane and carbon dioxide through the catabolism of various microorganisms with different functions. The collected biogas passes throughGenerator setThe engine performs combustion work, which is the form of an internal combustion engine. The torque after work drives the rotor windings of the generator to work, completing the power generation process.
3. Biogas requirements of 135 biogas generator set
The impurity content in biogas such as Si, HS, etc. should be controlled within the corresponding range. The temperature of biogas is 10~60 ℃ and the pressure is 0~5kpa. Generally, biogas treated anaerobically of poultry and livestock manure can meet the temperament requirements of power generation. Sewage Treatment of biogas requires desulfurization and other treatments, while landfill biogas requires dehydration and other treatments.
4. Precautions for use
Do not add more engine oil than the highest mark on the dipstick. Overfilling may cause damage to the engine.
Refill new engine oil from the filling port (in the direction of the arrow). After filling, start the engine and let it run at low speed for a few minutes
Used engine oil and oil filters are service waste. To prevent environmental pollution, regulations should be followed.
In some cases, if you need to open the cooling ducts while the engine is hot, read the manufacturer's instructions carefully.
5. Company Profile
Jiangsu Haixing Power Engineering Co., Ltd., located in Guxi Industrial Park, Taixing City, Jiangsu Province, is a professional manufacturer integrating the production, sales and maintenance of generator sets. The company mainly produces Dongfeng Fengshen generator sets, Dongfeng Cummins generator sets, Dongfeng Renault generator sets and Volvo generator sets, among which Dongfeng Cummins generator sets are sold at home and abroad.
Since its establishment, the company has continuously focused on the technical research and development of 135 biogas generator sets, expanded production scale, improved generator set-related services, and gradually developed into a new modern private enterprise in Taizhou City. The company has a complete organization and management system, rich human resources, advanced technology research and development and process equipment capabilities, and complete testing equipment. The 'Haixing' brand 20-2000Kw diesel generator sets produced are widely used in shipping, petrochemical industry, highways, railways, water conservancy hubs, municipal engineering, postal and telecommunications, industrial and mining enterprises, hotels and other fields.
6. Main parameters
Generator set model | Engine model | Generator model | Rated power(KW) | Maximum output power | Speed(r/min) | form | Cylinder volume (L) | Bore/stroke mm | Piston speed (m/s) | Intake method/combustion system |
24GFT49 | 2135T | IFC6-185-4 | 24 | 30 | 1500 | 4 stroke inline 2 cylinder | 4 | 135/140 | 7 | Naturally aspirated, non-supercharged/electronic ignition |
30GFT50 | 2135T | IFC6-223-4 | 30 | 37 | 1500 | 4 stroke inline 2 cylinder | 4.3 | 135/150 | 7.5 | |
40GFT51 | 4135T | IFC6-224-4 | 40 | 59 | 1500 | 4 stroke inline 2 cylinder | 8 | 135/140 | 7 | |
50GFT52 | 4135T | IFC6-225-4 | 50 | 73 | 1500 | 4 stroke inline 2 cylinder | 8.6 | 135/150 | 7.5 | |
64GFT22 | 6135T-1 | IFC6-226-4 | 64 | 83 | 1500 | 4 stroke inline 2 cylinder | 2 | 135/140 | 7 | |
75GFT60 | 6135T-2 | IFC6-282-4 | 75 | 88 | 1500 | 4 stroke inline 2 cylinder | 12 | 135/140 | 7 | |
90GFT32 | 6135T-1 | IFC6-283-4 | 90 | 110 | 1500 | 4 stroke inline 2 cylinder | 12.9 | 135/150 | 7.5 | |
100GFT35 | 6135T-2 | IFC6-283-4 | 100 | 120 | 1500 | 4 stroke inline 2 cylinder | 12.9 | 135/150 | 7.5 | |
120GFT54 | 6138AT-2 | IFC6-284-4 | 120 | 139 | 1500 | 4 stroke inline 2 cylinder | 13.9 | 138/163 | 8.1 | |
150GFT57 | 12V135T | IFC6-286-4 | 150 | 170 | 1500 | 4 stroke inline 2 cylinder | 24 | 135/140 | 7 | |
250GFT61 | 12V138AT | IFC6-353-4 | 250 | 280 | 1500 | 4 stroke inline 2 cylinder | 27.6 | 138/155 | 7.9 |
Generator set model | Compression ratio | direction of rotation | Total oil capacity (L) | Total cooling water capacity (L) | cooling system | Exhaust smoke temperature | Operation type | Natural gas consumption (m3/h) | Engine oil consumption (liter/hour) |
24GFT49 | 11 | Counterclockwise rotation when viewed from the direction of the flywheel | 20 | 100 | Water cooling/50% purified water plus 50% ethylene glycol-based antifreeze/inhibitor | ≤430 | Continuous power generation, as long line or base load power supply | 7 | 0.04 |
30GFT50 | 11 | 20 | 100 | ≤440 | 8.6 | 0.041 | |||
40GFT51 | 10 | 20 | 120 | ≤420 | 11.5 | 0.07 | |||
50GFT52 | 10 | 20 | 120 | ≤430 | 14.2 | 0.08 | |||
64GFT22 | 10.5:1 | 30 | 150 | ≤450 | 18.2 | 0.08 | |||
75GFT60 | 10.5:1 | 30 | 150 | ≤470 | 21 | 0.083 | |||
90GFT32 | 10.5:1 | 30 | 150 | ≤500 | 25.3 | 0.089 | |||
100GFT35 | 10.5:1 | 30 | 150 | ≤530 | 28 | 0.09 | |||
120GFT54 | 10.5:1 | 30 | 150 | ≤550 | 33 | 0.099 | |||
150GFT57 | 10.5:1 | 30 | 210 | ≤470 | 41 | 0.105 | |||
250GFT61 | 10.5:1 | 60 | 300 | ≤585 | 70 | 0.2 |